Skip to main content

Simulated Testing Algorithm for µPMU Full Observation of Balanced Radial Distribution Grid

مؤلف البحث
Wael Ahmed, Ibrahem Hassan, Ibrahem Hassan, M. Nayel, Hossam Gaber
المشارك في البحث
سنة البحث
2019
مجلة البحث
Conference: 2019 IEEE 7th International Conference on Smart Energy Grid Engineering (SEGE)
الناشر
NULL
عدد البحث
NULL
تصنيف البحث
3
صفحات البحث
NULL
موقع البحث
NULL
ملخص البحث

Today’s electric power distribution systems with development of distributed energy resources introduce variability, uncertainty, and opportunities to recruit diverse resources for grid services. Multiple resources on each feeder have more complex impacts on the circuit behavior that can be observed with voltage and current phase angle variations. Micro Phasor Measurement Units (μPMUs) take timesynchronized measurements of voltage, current and frequency that can tell grid operators what is happening, where, and when. This paper presents a new μPMUs power flow algorithm for complete observation of balanced radial distribution grid. This algorithm calculates all voltages in both high and low voltage buses, currents in all branches, line active and reactive power flow in all branches and total active and reactive power losses in the grid. This algorithm provides high quality data for distribution planners and operators, which will translate into better model accuracy and thus better results from distribution analysis tools. To test the validity of proposed algorithm, backward / forward sweep power flow program is developed and tested by ETAP software.