Performance analysis and working fluid selection for single and two stages vapor compression refrigeration cycles

مؤلف البحث
B. Saleh, Ayman A. Aly, M. Alsehli, A. Elfasakhany, M. M. Bassuoni
تاريخ البحث
سنة البحث
2020
مجلة البحث
Processes
الناشر
MDPI
عدد البحث
8
صفحات البحث
13
مستند البحث
موقع البحث
https://www.mdpi.com/2227-9717/8/9/1017
ملخص البحث

Screening for alternative refrigerants with high energy eciency and low environmental
impacts is one of the highest challenges of the refrigeration sector. This paper investigates the
performance and refrigerant screening for single and two stages vapor compression refrigeration
cycles. Several pure hydrocarbons, hydrofluorocarbons, hydrofluoroolefins, fluorinated ethers,
and binary azeotropic mixtures are proposed as alternative refrigerants to substitute R22 and R134a
due to their environmental impacts. The BACKONE equation of state is used to compute the
thermodynamic properties of the candidates. The results show that the maximum coecients
of performance (COP) for single and two stage cycles using pure substances are achieved using
cyclopentane with values of 4.14 and 4.35, respectively. On the other side, the maximum COP for the
two cycles using azeotropic mixtures is accomplished using R134a + RE170 with values of 3.96 and
4.27, respectively. The two-stage cycle presents gain in COP between 5.1% and 19.6% compared with
the single-stage cycle based on the used refrigerant. From the obtained results, among all investigated
refrigerants, cyclopentane is the most suitable refrigerant for the two cycles from the viewpoint of
energy eciency. However, extra cautions should be taken due to its flammability