Skip to main content

THE EFFECT OF USING FALSE CEILINGON ROOF COOLING LOAD

Research Authors
ALI H. Abdel-Razek, Ibrahim S. Taha, Mahmoud G.Morsy and Ali K. Abdel-Rahman

Research Member
Research Year
2014
Research Journal
Journal of Engineering Sciences Assiut University
Faculty of Engineering
Research Vol
42-3
Research Rank
2
Research_Pages
666–682
Research Abstract

Using of false ceilings (FC) for decoration and covering different ducts in modern buildings is
spreading so much nowadays. This paper tries to find a new employment and other benefits for
using false ceilings (FC).A one dimensional transient mathematical model has been established to
study the effects of using false ceiling on reduction of heat gained from concrete roof of controlled
temperature space. The effect of using false ceiling (FC), with and without adding reflector sheet on
its upper side facing to concrete roof on the room cooling load is studied by modeling and solving
the transient heat transfer processes in the different components of the space. The results showed
that using of false ceiling only without reflector sheet reduces heatgain introduced to space through
24 hours by 66.8%, while using of false ceiling with reflector sheet increases the reduction percent
of heat gained from concrete roof to be 81.6% for the same period.