In this paper, a new proposal for the implementation of the well-known direct power control (DPC) technique in grid-connected photovoltaic (PV) systems is suggested. Normally, the DPC is executed using a look-up table procedure based on the error between the actual and reference values of the active and reactive power. Thus, the structure of the DPC is simple and results in a fast transient behavior of the inner current loop (injected currents). Therefore, in the current study, the DPC is reformulated using a dead-beat function. In this formulation, the reference voltage vector (RVV) is obtained in the